Specification:
 
click for full photo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

5197 hardware, V3.1 Dec 1999 software

Function: Switches the DC output of a corrosion protection power supply synchronously with other units at other sites.

Switching current: 100 A DC maximum, over-current protection.
Switching voltage: 75 V DC maximum, over-voltage and reverse voltage protection.

Voltage drop across switch: 0.5 V maximum at 100 A.
Switch terminals: Brass terminal posts 8 mm ISO coarse 1.25 mm pitch.
Power: Internal battery - NiCd, 6 cell, 7.2 V, 500 mAh.

Battery charger: Mains or 12 V external battery - 14 hours for full charge. For best stability, and to keep the battery charged, all units should be on charge at all times.

Battery discharge time: 12 hours.
Relative drift between instruments after synchronising:60 ms over 106 hours (7 am Monday till 5 pm Friday) typical. 5 to 25 øC. 150 parts per billion typical.

Serial connection: RS232C for adjusting the on and off times, clock and survey times on the unit chosen to be the master. Not electrically isolated from the switch.
Range of on and off times: 60 ms to 30 000 ms (0.06 to 30 s) in 10 ms steps.

Synchronising Line-Trek to Line-Trek: Serial cable connection between a unit chosen as master and any other unit as a slave. Pressing the master's pushbutton initiates the synchronisation.

External Synchronism: Capable of synchronisation with a Miller J1 or J2 model interrupter in both directions - with a delay to handle Miller relay pull-in/release time. An externally applied +5 to 0 V transition or contact closure will synchronise the Line-Trek so that its switch will be turned on after the set delay. Pressing the Line-Trek's pushbutton will initiate a 0.5 second +5 to 0 to +5 V pulse, the front edge of which will occur the set delay before the next available Line-Trek switch on time.
RS232C Connector: DB9 male. Cable: Null modem for synchronising and PC communication.

Electrical isolation: isolated between case and switch.
Not isolated between RS232 ground (pin 5) and the switch. RS232C pin 5 and the synchronising common are connected internally to the - terminal. Do not connect an earthed computer to the unit when the switch is connected in circuit. A laptop running on its internal battery may be used.

Temperature range: -20 to +50 øC.

Humidity: 0 to 95% non condensing.

Size: 200 x 179 x 88 mm.

Weight: 2.7 kg.

Case: black anodised aluminium and polyester powder coated steel.

Designed and manufactured by: Solid State Equipment Ltd, Lower Hutt, New Zealand

Home Page